Assessing existing radiators for low temperatures in retrofit applications

As we enter our second year since the launch of the ‘Low Temperature Heating and Hot Water Systems in Dwellings‘ qualification, we have witnessed a notable increase in the interest of installers looking to specialise in low-temperature heating systems, particularly heat pumps. The Chartered Institute of Plumbing and Heating Engineering (CIPHE) has been hard at work updating the Plumbing Engineering Services Design Guide, introducing a substantial new section dedicated to heating. This new section comprises over 300 pages of content, featuring 70 illustrations and more than 60 calculations. The CIPHE firmly believes that this comprehensive resource is crucial for the professional growth of installers in this field.

Challenges in retrofitting low-temperature heat pump systems

Retrofitting low-temperature heat pump systems presents unique challenges, one of which is the need to not only understand the heat loss of each room but also evaluate the performance of existing radiators to assess their suitability for lower-temperature applications. It is common to find oversized radiators during installation, but with some knowledge and effective system balancing, it is often possible to optimise the existing heating system.

How to optimise a heating system

Step 1: Calculating room heat loss

The first crucial step in optimising low-temperature heat pump installations is to calculate the heat loss for each room. This information serves as the foundation for making informed decisions regarding radiator selection and system adjustments.

Step 2: Determining existing radiator output

Understanding the actual rated output of radiators is vital. Radiators typically fall into three main types: K1, K2, and P+. These categories share similar output characteristics among various manufacturers. However, older legacy radiators can be more challenging to identify. The CIPHE's “supplementary radiator guide” is a valuable resource that presents various radiator factors in Watts per square meter (W/m2). By measuring the radiator's surface area or the number of columns and multiplying the appropriate factor from the guide, one can estimate the rated output at a delta T of 50 (DT50). The radiator DT50 is the published output from manufacturers which is the (radiator mean water temperature – the room temperature)^1.3. Each manufacturer radiator will have a variety of n exponents, however for simplicity we will use 1.3.

Step 3: Calculating the required flow rate

To determine the required flow rate to the radiator based on the room heat loss, you can use the formula:

(Room heat loss (kW) / (DT * 4.19) = flow rate (l/s)

For instance, with a DT of 5 and a room heat loss of 1kW (1,000 Watts), the required flow rate would be 0.047 l/s.

Step 4: Calculating the radiator's new mean water temperature (MWT)

Selecting the appropriate flow temperature and system DT is crucial when designing a heating system, with DT of 5 being common for heat pumps. For instance, consider an existing retrofit installation with a heat loss of 1,000W and an existing radiator rated at 3,500 Watts at DT50. To determine the radiator's output at a lower mean water temperature (MWT), a new flow temperature and DT must be chosen. A common choice might be a flow temperature of 45°C and a DT of 5°C.

The radiator's MWT is calculated as 45 - (5/2) = 42.5. Therefore, with a room temperature of 20°C, the new radiator MWT - Air = (42.5 - 20) = 22.5.

Step 5: Calculating the output of the radiator at the new MWT

The next step is to calculate the output of the radiator under these new proposed conditions. The question is whether the existing oversized radiator can deliver 1,000 Watts at the new lower temperatures.

What you need to know

To calculate the radiator factors F1, F2, F3, and F4 as per the EN 442 standard, you need to know how the pipework is connected to the radiator (F2), the location of the radiator (F3), and its surface finish (F4). For this example, the radiator is installed on a plain wall, with bottom opposite end pipe connections (BOE) and a water-based paint finish.

The following formula can be applied for F1:

F1 = (new radiator MWT - Air) / 50) ^ 1.3

In our example, the F1 factor would be:

F1 = (22.5 / 50) ^ 1.3 ≈ 0.354

Following this, you would select the other correction factors from the DHDG.

F2 = 0.96, F3 = 1, and F4 = 1

Therefore, the new radiator output at the lower temperatures is:

3,500 Watts * 0.354 * 0.96 * 1 * 1 = 1,189.44 Watts

Interpreting the result

As you can see, the new radiator would still deliver an additional output of 189.44 Watts above the required heat loss, which would require some form of TRV to regulate the radiator from overheating the room.

How to achieve 1,000 Watts output

If the radiator was to be installed into an open circuit heat pump system (without TRVs), then the radiator MWT would need to be matched exactly to the room heat loss. To enable you to calculate the required radiator MWT to achieve a 1,000 Watts output you would calculate as follows:

Calculate new radiator factor = (heat loss / (existing radiator output * F2 * F3 * F4)

(1,000 / (3,500 * 0.96 * 1 * 1) = 0.297

By transposing the simple formula, you arrive at the following:

((0.297)^(1/1.3)) * DT50) + 20 (room temperature) = 39.68°C

Therefore, the new flow temperature with a system DT of 5 would need to be 39.68°C + (5/2) = 42.18°C.

Multiple radiators

In a scenario where there are multiple radiators installed in to a system after a buffer tank, then each radiator DT would need to be balanced separately once the highest radiator MWT has been calculated. In existing retrofit applications where the pipework may not be suitable for a heat pump system with higher flow rates, this method with hydraulic separation can be used to avoid costly pipework upgrades.

Conclusion

Optimising low-temperature heat pump installations in retrofit applications involves careful consideration of heat loss, radiator characteristics, and flow temperature selection. By following the steps outlined above, installers can make existing heating systems more efficient and enhance overall comfort. The resources and guidance provided by organisations like the CIPHE play a pivotal role in equipping professionals with the knowledge and skills required to excel in this increasingly important field of heating technology.

You might also like

The role of heat interface units (HIUs) in modern heat networks

The role of heat interface units (HIUs) in modern heat networks

How to install press-fit pipework for ACR systems

How to install press-fit pipework for ACR systems

How to achieve optimal water flow rates and pressure

How to achieve optimal water flow rates and pressure